140° opening single-leaf natural smoke ventilator up to 2.5m² GFA. For flat and pitched roofs. EN 12101-2 certified with 24V actuator. Vent Trade.
- up to 2.5m²
- Roof 140° opening
- 24v
- Poly, insulated or dome

Certified to BS EN 12101-2 with Re 300 smoke extraction reliability and B 300 resistance to 300°C. Opens in under 60 seconds for rapid smoke dispersal.
From 1.26m² to 9.5m² geometric free area, the LAM scales to suit any project requirement. Standard sizes in stock for next day despatch, bespoke sizes on request.
Installs at any angle from horizontal to vertical. Turn-down flange suits a 150mm high, 90mm wide finished upstand. Custom flange widths from 70mm to 320mm.
Standard sizes deliver 1.26m² or 1.8m² geometric free area, with bespoke configurations available up to 9.5m² GFA for large-scale smoke ventilation requirements.
Suitable for installation angles from 0° to 90°. Standard horizontal roof mount includes aluminium wind deflector. Vertical facade mount available with optional rain shield.
Each unit is supplied preassembled for straightforward installation, with non-standard flange options available to suit various roofing and facade types.
Standard 1.25mm aluminium blades. Non-standard options include aluminium with XPS insulation, clear or opal polycarbonate in 16mm or 25mm thicknesses.
Standard widths from 800mm (4 blades) to 3600mm (18 blades) with lengths in 200mm increments, enabling precise sizing for any structural opening.
Re 300 reliability for smoke extraction and Re 10000 for daily environmental ventilation, providing long-term operational dependability for both duties.
1200mm(W) x 1400mm(L) structural opening. 6 blades. Aerodynamic free area 1.06m². Weight 46 kg. Current draw 0.8 amps.
1200mm(W) x 2000mm(L) structural opening. 6 blades. Aerodynamic free area 1.53m². Weight 71 kg. Current draw 1.0 amps.
Min 500mm(L) x 800mm(W), max 2200mm(L) x 3800mm(W). Up to 9.5m² GFA. Non-standard sizes may not be tested to BS EN 12101-2.
Vertical LAM option with rain shield available on request for facade-mounted smoke ventilation applications.
Certified for smoke and heat exhaust ventilation systems. Both standard sizes independently tested and verified for UK smoke ventilation standards.
Operational reliability rated Re 300 for smoke extraction and Re 10000 for daily environmental ventilation duty cycles.
Smoke ventilation systems require regular testing and record-keeping by authorised, competent persons. Servicing by accredited and certified smoke vent engineers only.
We have a team of ventilation specialists on hand to help guide you towards selecting and customising your system.
Call us: 01202 725 485
Email us: info@vent-trade.co.uk