UK smoke ventilation tool

THE Free Area Calculator

Calculate Aerodynamic Free Area (Aa) for AOV windows, louvres, roof vents and smoke shaft dampers. This tool uses SCA Guidance on Smoke Control (Smoke Control Association Guidance on Smoke Control to Common Escape Routes in Apartment Buildings, Rev 3.1) to check sizing against UK building regulations including Approved Document B and BS 9991.

  • Approved Document B
  • BS 9991
  • BS 9999
  • BS 7346
  • BS EN 12101-2

Free Area Calculator

Not sure which scenario? Tell us about the project →
Building type
Height (above ground)
Has basement?

Fill in the details above to see a scenario recommendation.

Heuristic only: always confirm against the project fire strategy.

1 What are you sizing for?
2 Vent type
3 Size it
Discharge coefficient (Cv): bottom-hung default 0.50

Note on louvres: the generic Cv 0.65 may understate some louvres (Vent Trade louvres test at Cv 0.83–0.85). For certified sizing, use product mode or your product's Declaration of Performance.

A fast first-pass check for UK specifiers, M&E contractors, fire engineers and building control sizing AOVs, smoke roof vents, louvres and dampers against Approved Document B, BS 9991, BS 9999, BS 7346 and the relevant BS EN 12101 parts.

How it works

Pick a scenario (e.g., common corridor, stair head, smoke shaft) and the target aerodynamic free area (Aa) loads automatically with the regulation citation. Pick a vent type and the calculator applies a sensible generic discharge coefficient (Cv) based on UK manufacturer datasheets. Then either enter the opening dimensions or pick a Vent Trade product configuration: the latter uses the manufacturer’s certified BS EN 12101-2 / -8 aerodynamic free area directly, no Cv guessing.

Hinged smoke windows (bottom-hung, side-hung) apply a sin(angle) correction; louvres and dampers are treated as fully open.

Note on smoke windows: AOV smoke windows are typically bottom-hung so the aperture sits at the top of the frame, where the hot smoke layer collects. Top-hung windows (opening at the bottom) are used for daily natural ventilation, not smoke clearance: they’re deliberately excluded from the calculator.

Why aerodynamic, not geometric?

UK building regulations (Approved Document B, BS 9991, BS 9999) allow free-area sizing to be measured as either geometric area per traditional methods (ADB Appendix D, Diagram D7) or as aerodynamic free area (Aa) per BS EN 12101-2. The SCA prefers Aa because it directly reflects a certified product’s tested performance. This calculator uses Aa targets per SCA Guidance (0.9 m² Aa for the corridor, 0.7 m² for the stair); if you prefer geometric area, add roughly 60–70% to the Aa target.

Certified Vent Trade products achieve Cv ranges varying by product: windows 0.61–0.70, louvres 0.83–0.85. The generic defaults shown here (0.50–0.70) are a conservative first-pass only for estimation; always use the manufacturer’s certified Aa from the Declaration of Performance for final sizing.

Common UK targets

ScenarioStandardRequired Aa
Common corridor / lobbySCA Guidance (ADB equivalent)0.9 m²
Stair head AOVSCA Guidance (ADB equivalent)0.7 m²
Smoke shaft AOV at each storeyBS 9991:2015 §14.2.3.21.0 m²
Single-stair residentialBS 9991:2015 §14.1.20.7 m²
Non-residential stairBS 9999:2017 §27.11.0 m²
BasementApproved Document B Vol 12.5% of floor area

Taller buildings, single-stair designs and basements often exceed these: always check the project fire strategy and the Smoke Control Association technical guidance.

Indicative only: confirm against the manufacturer’s tested BS EN 12101-2 / -8 Declaration of Performance. Pair with our Smoke Ventilation Guide and BS EN 12101 overview for full context.

Free area calculator: FAQs

What is aerodynamic free area (Aa)?

Aerodynamic free area, written Aa, is the effective area for airflow once turbulence and edge losses are accounted for. It is calculated as Aa = geometric area × Cv, where Cv is the discharge coefficient measured under BS EN 12101-2. Aa is the value that must satisfy BS 9991, BS 9999 and Approved Document B.

What free area does Approved Document B require?

Approved Document B Volume 1 requires 1.5 m² free area in the common corridor or lobby (para 3.51(a)) and 1.0 m² at the head of the stair (para 3.52). Per ADB Appendix D5, this ‘free area’ can be measured as either geometric area or declared aerodynamic free area (Aa) per BS EN 12101-2. The SCA Guidance on Smoke Control (Rev 3.1) interprets these as equivalent to 0.9 m² Aa (corridor) and 0.7 m² Aa (stair). This calculator uses the SCA equivalence to ensure compliance.

Does opening angle change the free area of an AOV window?

Yes. A bottom-hung or side-hung AOV window only achieves its full geometric area at 90°. At 30° the projected opening is roughly half. The calculator applies sin(angle) to the geometric area for hinged vents, which mirrors the convention used in most UK AOV datasheets.

Why bottom-hung rather than top-hung for smoke AOVs?

Hot smoke rises, so the opening needs to be at the top of the window for it to escape. A bottom-hung window (hinged at the sill) opens outward at the top, putting the aperture where the smoke layer collects. Top-hung windows (hinged at the head) open at the bottom: fine for everyday natural ventilation, not effective for smoke clearance.

What is the difference between an EN 12101-2 louvre and an EN 12101-8 damper?

BS EN 12101-2 covers natural smoke and heat exhaust ventilators (NSHEVs): typically louvred outlets at the head of a smoke shaft or external smoke louvres. BS EN 12101-8 covers smoke control dampers: motorised dampers inside smoke shafts, on corridor extract grilles, or in mechanical extract ducts. Both are sized on their certified Aa, but the test regimes and leakage classifications differ. For sign-off use the certified figure from the relevant Declaration of Performance.

Can I override the discharge coefficient?

The calculator uses sensible defaults based on UK manufacturer datasheets (Cv 0.50 for bottom-hung, 0.55 for side-hung, 0.65 for louvres and dampers, 0.70 for roof vents). These generic defaults apply the coefficient to the full face or projected opening and are conservative for estimation. For louvres and dampers especially, always verify against your product’s certified Aa in the Declaration of Performance: Vent Trade louvres typically achieve Cv 0.83–0.85 against the throat area. For final sizing and sign-off, use the product-picker mode or the manufacturer’s certified Aa directly.

What does the SCA recommend for sizing AOVs?

The SCA Guidance on Smoke Control to Common Escape Routes (Rev 3.1) sets aerodynamic free area targets: 0.9 m² Aa for the ADB 1.5 m² common-corridor figure (para 3.51(a)), and 0.7 m² Aa for the 1.0 m² stair-head figure (para 3.52). This calculator uses these SCA-endorsed Aa equivalences as the baseline targets. Always use the manufacturer’s certified Aa from their BS EN 12101-2 or BS EN 12101-8 Declaration of Performance, not the generic Cv defaults shown here.

What's the difference between the calculator's generic Cv and a product's certified Cv?

Generic Cv values are typical-case figures used when the actual vent isn’t known yet: they’re conservative on purpose. A certified Cv comes from a BS EN 12101-2 / -8 test conducted on a specific product configuration. When you toggle the calculator to ‘Pick a Vent Trade product’ mode, the result uses the certified Aa directly and computes the implicit Cv for reference. For louvres and dampers especially, generic Cv 0.65 may understate actual performance: Vent Trade louvres typically achieve Cv 0.83–0.85. For final sizing, always use the product-picker mode or refer to your product’s Declaration of Performance.

Can I use the calculator for basement smoke clearance?

Yes: pick the ‘Basement’ scenario chip. Basement smoke ventilation is typically sized at 2.5% of the basement floor area (per BS 7346-4 / common UK convention). The calculator multiplies your floor-area input by 0.025 to set the target Aa.