Why Choose the Ventec OSTRO Access

Smoke Ventilation + Roof Access

Combines certified BS EN 12101-2 smoke ventilation with safe roof access capability. Offset actuator design enables full lid opening for maintenance personnel.

Document L Compliant

U-value of 2.92 W/m²K meets Approved Document L thermal performance requirements. Insulation options allow customisation to project-specific thermal targets.

Versatile Application

Suitable for flat and pitched roofs up to 15° across production halls, logistics centres, public buildings, commercial properties and residential developments.

Key Features

Roof Access

Side-positioned 24Vdc actuator allows the lid to be fully opened for safe maintenance access to the roof, combining ventilation with practical functionality.

140° Opening Angle

Single-leaf design opens to 140° for maximum smoke and heat dispersal. Rapid opening in under 60 seconds for emergency smoke ventilation.

Document L Compliant

Overall U-value of 2.92 W/m²K meets Approved Document L thermal performance requirements, ensuring energy efficiency compliance.

Straight Overlay Base

200mm high straight base made from 1.25mm thick galvanised steel sheet with circumferential strip for secure roof integration and ease of installation.

Multiple Lid Options

Standard 10mm opal polycarbonate lid. Options include clear polycarbonate, 20mm and 25mm thicknesses, dome configurations and sandwich panel lids.

Customisable Base

Thermal insulation type and thickness adjustable to individual requirements. Standard 30mm PIR panel insulation with mineral wool option. RAL colour finishes available.

Choose Your Configuration

Standard

1.06m² GFA

Standard in-stock size with 1100mm x 1100mm structural opening. 10mm opal polycarbonate lid. 30mm PIR insulated galvanised steel base. Weight approx. 100 kg.

Bespoke

Custom Options

Non-standard sizes, lid options and base insulation configurations available on request. Flange profile customisable to suit various roofing types.

Certifications & Compliance

BS EN 12101-2

Certified for natural smoke and heat exhaust ventilation systems. Independently tested and verified for UK smoke ventilation standards.

Approved Document L

Compliant with Approved Document L thermal performance requirements with U-value of 2.92 W/m²K for the standard configuration.

Regular Servicing Required

Smoke ventilation systems require regular testing and record-keeping by authorised, competent persons. Servicing by accredited and certified smoke vent engineers only.

Need Some Help?

We have a team of ventilation specialists on hand to help guide you towards selecting and customising your system.

Call us: 01202 725 485

Email us: info@vent-trade.co.uk

Technical Specifications

Performance

  • Geometric Free Area: 1.06m²
  • Aerodynamic Free Area: 0.74m²
  • Certification: BS EN 12101-2
  • Compliance: Approved Document L
  • Maximum Opening Angle: 140°
  • Opening Time: < 60 seconds
  • Reliability (Smoke): Re 50
  • Reliability (Daily): Re 10000
  • Snow Load: SL 250
  • Wind Load: WL 1500
  • Operating Temp Low: -25°C
  • Resistance Temp High: B 300 (300°C)

Electrical

  • Operating Voltage: 24Vdc
  • Current Consumption: 1.6 amps
  • Cable Cores: 2 Core + Earth

Physical

  • Structural Opening: 1100mm(W) x 1100mm(L)
  • Upstand Outer (max.): 1500mm(W) x 1500mm(L)
  • Flange Outer: 1560mm(W) x 1560mm(L)
  • Base Cover Outer: 1566mm(W) x 1566mm(L)
  • U-value: 2.92 W/m²K
  • Base Material: 1.25mm galvanised steel
  • Base Insulation: 30mm PIR panel (standard)
  • Lid: 10mm opal polycarbonate (standard)
  • Upstand Height: 150mm (min.)
  • Flange Width: 230mm (standard)
  • Weight: Approx. 100 kg
  • Roof Pitch: Flat to 15°