140° opening single-leaf natural smoke ventilator up to 2.5m² GFA. For flat and pitched roofs. EN 12101-2 certified with 24V actuator. Vent Trade.
- up to 2.5m²
- Roof 140° opening
- 24v
- Poly, insulated or dome

Certified to BS EN 12101-2 with Re 1000 smoke extraction reliability. 90° blade opening delivers up to 1.62m² aerodynamic free area in under 60 seconds.
U-value from 2.07 W/m²K ensures compliance with Approved Document L. Mineral wool insulated blades and base provide excellent thermal performance when closed.
Delivers high geometric free area from a compact footprint. Two standard sizes suit 1.0m² or 1.5m² GFA regulation requirements without oversized structural openings.
Designed for horizontal mounting on roofs or vertical mounting on facades. Blade axis remains horizontal in all installations. Rain shield or structural canopy recommended for facade use.
Five aluminium blades open to 90° for maximum aerodynamic free area. Mineral wool insulated blades for thermal performance when closed.
Each unit is supplied preassembled for straightforward installation, reducing on-site labour and commissioning time.
U-value as low as 2.07 W/m²K meets Approved Document L thermal performance requirements for energy-efficient building envelopes.
Overlay type base for installation on a finished upstand with 220mm all-round flange and 40mm drip cap for weather-tight integration.
Aluminium base and blade construction with mineral wool insulation. Lightweight yet robust with weights from 70 kg to 100 kg depending on size.
1400mm(W) x 1186mm(L) structural opening. 5 blades. Aerodynamic free area 1.06m². U-value 2.07 W/m²K. Weight 70 kg. Current draw 1.0 amps.
2100mm(W) x 1186mm(L) structural opening. 5 blades. Aerodynamic free area 1.62m². U-value 2.18 W/m²K. Weight 100 kg. Current draw 1.0 amps.
Non-standard sizes available on request. Base insulation and blade material options can be specified. Vertical facade installation with rain shield available.
Certified for smoke and heat exhaust ventilation systems. Both standard sizes independently tested and verified for UK smoke ventilation standards.
Compliant with Approved Document L thermal performance requirements. U-value 2.07 W/m²K (1.27m² size) and 2.18 W/m²K (1.92m² size).
Smoke ventilation systems require regular testing and record-keeping by authorised, competent persons. Servicing by accredited and certified smoke vent engineers only.
We have a team of ventilation specialists on hand to help guide you towards selecting and customising your system.
Call us: 01202 725 485
Email us: info@vent-trade.co.uk