AOV Controls: Smoke Control Panels UK

Complete AOV Control Solutions: From Single-Zone Panels to Full System Integration

Product Overview

Smoke Control Panels & Override Components

BS EN 12101-10certified
Made in UKmanufactured
O Rangesystem

AOV control components are the interface between a building’s fire alarm and its smoke ventilation equipment: receiving detection signals, managing cause and effect sequences, powering actuators, and providing firefighter override capability. Vent Trade supplies the complete O Range control system, manufactured in the UK to BS EN 12101-10, covering panels, status indication, override switches, detectors, and commissioning tools.

Smoke Accessories
O Range CSP visual status panel for smoke ventilation systems
O RangeCSP

Visual status panel for O Range smoke control. Fire, Fault and Healthy LEDs at a glance. Brushed steel finish, standard pattress box. EN 12101-10 compliant.

  • O Range compatible
  • Networkable
  • Fire / Fault / Healthy
Smoke Accessories
O Range firefighter override switch for smoke ventilation
O RangeFirefighter Switch

Manual override for smoke ventilation systems. Open or close smoke vents directly from stairwells and lobbies. Surface or flush mount. O Range compatible.

  • O Range compatible
  • prEN 12101-9
  • 1 zone control
  • Smoke + enviro
Smoke Accessories
O Range Connect Tool for on-site panel configuration and diagnostics
O RangeConnect Tool

Hardware commissioning tool for on-site O Range panel configuration, testing, and diagnostics. O Range Connect Tool connects to the O Range to allow configuration and monitoring of the software.

  • O Range compatible
  • 1 to 60 zones
  • Engineer 2FA
  • Golden Thread
Smoke Accessories
O Range optical smoke detector with relay base
O RangeSmoke Detector

Photoelectric smoke detector for O Range systems. 9–33Vdc operating range with relay base option. Ceiling or wall mount. Plug-and-play installation.

  • O Range compatible
  • 9-33Vdc range
  • Photoelectric

AOV control components certified to BS EN 12101-10: including O Range and Ventec 400 Series smoke control panels, firefighter switches, status indication, and detection. Substantial stock held for same-day despatch.

For help selecting the right control components, call our technical team on 01202 725 689.

Frequently Asked Questions

What are AOV controls?

AOV controls are the electronic components that manage the operation of Automatic Opening Vent systems in buildings. They encompass smoke control panels, firefighter override switches, smoke detectors, battery backup units, and commissioning software: everything between the fire alarm signal and the actuator that opens the vent.

The smoke control panel is the central component, receiving detection signals from the fire alarm system and powering the actuators to open smoke vents, dampers, and louvres in the correct sequence. AOV controls also provide firefighter override capability, allowing the fire service to manually control vent positions from the building entrance. Status panels display system health information including fire, fault, and healthy indications.

In the UK, AOV control equipment must be tested and certified to the relevant sections of BS EN 12101, ensuring reliable performance in life-safety applications where system failure could compromise escape routes during a fire.

How do I choose the right AOV control components?

Selecting AOV control components requires matching each element to the fire strategy and system design. Start with the smoke control panel: determine the number of zones, total actuator load in amps, and whether addressable or conventional control is required.

The Ventec 400 Series suits standard single-stairwell residential systems in 4A, 8A, 13A, and 20A ratings. The O Range 7 addressable panel handles multi-zone and networked installations up to 60 zones. Add a firefighter override switch: the O Range Firefighter Switch is built to prEN 12101-9. Position it at the main building entrance for fire service access.

Include a Control Status Panel where remote status indication is required for building management. If no building fire alarm exists, add O Range Optical Smoke Detectors for local detection. Finally, confirm that the battery backup capacity covers all connected loads for the required 72-hour standby period specified in BS EN 12101-10.

What standards do AOV control components need to meet?

AOV control components in the UK must comply with multiple sections of BS EN 12101, the European standard suite for smoke and heat control systems. The smoke control panel is built to prEN 12101-9, covering control logic, fault monitoring and system integration, with its power supply to BS EN 12101-10, which covers power supply reliability and battery backup duration of at least 72 hours.

The firefighter override switch is built to align with prEN 12101-9, ensuring reliable manual control for fire service use. Smoke detectors used within AOV systems should comply with BS EN 54 for fire detection equipment. The overall system installation must satisfy the fire safety requirements of Approved Document B of the Building Regulations in England, with equivalent requirements in Scotland and Wales.

Both the O Range and Ventec 400 Series control equipment supplied by Vent Trade are tested and certified to the relevant BS EN 12101 standards, with documentation available for building control submissions.

Where are AOV control components installed in a building?

AOV control components are distributed throughout the building according to the system design and fire strategy requirements. The smoke control panel is typically installed in a secure, accessible location at ground floor level: commonly the entrance lobby, electrical intake room, or a dedicated fire systems cupboard.

The firefighter override switch is mounted at the main building entrance where the fire service will arrive, clearly labelled and easily accessible. Control Status Panels providing remote indication are installed where building management staff need visibility of system status, such as reception desks, concierge stations, or facilities management offices.

Smoke detectors, where required, are positioned in protected escape routes according to the detection design. Battery backup units are housed within or adjacent to the panel enclosure. For networked multi-zone systems, satellite panels or zone expansion modules may be distributed across multiple locations within the building to minimise cable runs to distant actuator positions.

What maintenance do AOV control systems require?

AOV control systems are life-safety installations and require scheduled testing and maintenance in accordance with BS 7346-8. Weekly visual inspections should confirm all panel status indicators show a healthy system state with no fault or fire warnings.

Monthly functional tests must include full activation of all connected actuators, verification of cause and effect sequences between detection zones and vent groups, and confirmation that the firefighter override switch operates correctly. Battery backup should be tested quarterly by simulating a mains failure and confirming full system operation on battery power. Batteries should be replaced on the manufacturer’s recommended schedule, typically every three to five years, or sooner if load testing indicates reduced capacity.

A comprehensive annual service by a competent engineer should cover panel fault log review, actuator force and stroke testing, wiring integrity checks, detector cleaning and testing, and documentation of all results. Maintain a complete service log as part of the building’s fire safety management records.